Motor Full Load Current Chart (415 V)

Motor full-load current chart for 415 V three-phase induction motors from 0.37 kW to 160 kW (0.5 to 215 HP), with the matching contactor, overload relay and MPCB for each size.

Use it to size starters, cables and protection quickly. Values are typical for 4-pole IE2 motors at 415 V, 50 Hz. Always confirm with the current printed on your motor's nameplate. Prices checked 3 November 2026. Reviewed by Amit, Voltkart.

415 V motor full-load current chart (kW, HP and amps)

Motor kW HP Full-load current (415 V) Contactor (AC-3) Overload relay MPCB (up to 15 kW)
0.37 kW 0.5 HP 1.1 A LC1D09
₹1,421
LRD06
₹1,890
GV2ME06
₹4,670
0.55 kW 0.75 HP 1.5 A LC1D09
₹1,421
LRD06
₹1,890
GV2ME06
₹4,670
0.75 kW 1 HP 1.8 A LC1D09
₹1,421
LRD07
₹1,890
GV2ME07
₹4,670
1.1 kW 1.5 HP 2.6 A LC1D09
₹1,421
LRD08
₹1,890
GV2ME08
₹4,830
1.5 kW 2 HP 3.5 A LC1D09
₹1,421
LRD08
₹1,890
GV2ME08
₹4,830
2.2 kW 3 HP 5 A LC1D09
₹1,421
LRD10
₹1,890
GV2ME10
₹4,830
3 kW 4 HP 6.5 A LC1D09
₹1,421
LRD12
₹1,890
GV2ME14
₹4,830
3.7 kW 5 HP 7.5 A LC1D09
₹1,421
LRD14
₹2,120
GV2ME14
₹4,830
5.5 kW 7.5 HP 11 A LC1D12
₹1,600
LRD16
₹2,120
GV2ME16
₹5,410
7.5 kW 10 HP 15 A LC1D18
₹3,152
LRD21
₹2,200
GV2ME20
₹5,850
9.3 kW 12.5 HP 18 A LC1D25
₹2,305
LRD22
₹2,200
GV2ME21
₹6,220
11 kW 15 HP 22 A LC1D25
₹2,305
LRD22
₹2,200
GV2ME22
₹6,220
15 kW 20 HP 29 A LC1D32
₹8,116
LRD32
₹3,510
GV2ME32
₹10,074
18.5 kW 25 HP 35 A LC1D38
₹6,378
LRD35
₹3,510
–
22 kW 30 HP 42 A LC1D50
₹8,850
LRD350
₹5,330
–
30 kW 40 HP 57 A LC1D65
₹12,300
LRD365
₹6,840
–
37 kW 50 HP 70 A LC1D80
₹15,350
LRD3363
₹7,418
–
45 kW 60 HP 85 A LC1D95
₹19,800
LRD3365
₹9,157
–
55 kW 75 HP 103 A – – –
75 kW 100 HP 138 A – – –
90 kW 125 HP 165 A LC1E200
₹34,583
– –
110 kW 150 HP 200 A LC1E200
₹34,583
– –
132 kW 180 HP 240 A LC1E250
₹45,573
– –
160 kW 215 HP 285 A LC1E300
₹56,106
– –

Rule of thumb: about 2 A per kW at 415 V. Contactor and relay pairings are for direct-on-line starting; for star-delta, set the overload relay to about 58% of the full-load current.

Related tools

Full-load current by motor size: quick answers

What is the full-load current of a 5 HP (3.7 kW) motor?

A 5 HP (3.7 kW) three-phase motor draws about 7.5 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D09 contactor with an LRD14 overload relay, or a GV2ME14 MPCB. Check the motor nameplate for the exact current.

What is the full-load current of a 7.5 HP (5.5 kW) motor?

A 7.5 HP (5.5 kW) three-phase motor draws about 11 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D12 contactor with an LRD16 overload relay, or a GV2ME16 MPCB. Check the motor nameplate for the exact current.

What is the full-load current of a 10 HP (7.5 kW) motor?

A 10 HP (7.5 kW) three-phase motor draws about 15 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D18 contactor with an LRD21 overload relay, or a GV2ME20 MPCB. Check the motor nameplate for the exact current.

What is the full-load current of a 15 HP (11 kW) motor?

A 15 HP (11 kW) three-phase motor draws about 22 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D25 contactor with an LRD22 overload relay, or a GV2ME22 MPCB. Check the motor nameplate for the exact current.

What is the full-load current of a 20 HP (15 kW) motor?

A 20 HP (15 kW) three-phase motor draws about 29 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D32 contactor with an LRD32 overload relay, or a GV2ME32 MPCB. Check the motor nameplate for the exact current.

What is the full-load current of a 30 HP (22 kW) motor?

A 30 HP (22 kW) three-phase motor draws about 42 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D50 contactor with an LRD350 overload relay. Check the motor nameplate for the exact current.

What is the full-load current of a 40 HP (30 kW) motor?

A 40 HP (30 kW) three-phase motor draws about 57 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D65 contactor with an LRD365 overload relay. Check the motor nameplate for the exact current.

What is the full-load current of a 50 HP (37 kW) motor?

A 50 HP (37 kW) three-phase motor draws about 70 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D80 contactor with an LRD3363 overload relay. Check the motor nameplate for the exact current.

What is the full-load current of a 75 HP (55 kW) motor?

A 75 HP (55 kW) three-phase motor draws about 103 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D115 contactor. Check the motor nameplate for the exact current.

What is the full-load current of a 100 HP (75 kW) motor?

A 100 HP (75 kW) three-phase motor draws about 138 A at full load on 415 V (typical 4-pole IE2 motor). For a direct-on-line starter use an LC1D150 contactor. Check the motor nameplate for the exact current.

Motor current FAQs

How do I calculate the full-load current of a 3-phase motor?

Full-load current = kW × 1000 ÷ (√3 × voltage × power factor × efficiency). For a 7.5 kW motor at 415 V with a power factor of about 0.85 and efficiency of about 0.88: 7500 ÷ (1.732 × 415 × 0.85 × 0.88) ≈ 14 A, which is close to the 15 A in the chart. The motor nameplate always gives the exact figure.

Why is the current different on my motor nameplate?

Full-load current depends on the number of poles, efficiency class (IE1, IE2, IE3), power factor and the manufacturer. 2-pole and 6-pole motors and rewound motors can differ from the typical values here, so always set protection to the nameplate current.

What is the current of a 5 HP and a 10 HP motor at 415 V?

A 5 HP (3.7 kW) 3-phase motor draws about 7.5 A, and a 10 HP (7.5 kW) motor about 15 A at 415 V. A rough rule of thumb is about 2 A per kW at 415 V for small and medium motors.

How much current does a motor draw when starting?

A direct-on-line start draws about 6 to 7 times the full-load current for a few seconds. Star-delta starting reduces this to about one-third, and a VFD or soft starter limits it further.

What size contactor and overload relay do I need?

Choose a contactor whose AC-3 rating covers the motor kW, and an overload relay whose setting range includes the full-load current, then set it to the nameplate current. The chart above gives the usual Schneider pairing for 415 V DOL starters.

You are welcome to link to this chart from your own site or course notes.