Motor Full Load Current Chart (415 V)

Motor full-load current chart for 415 V three-phase induction motors from 0.37 kW to 75 kW (0.5 to 100 HP), with the matching contactor, overload relay and MPCB for each size.

Use it to size starters, cables and protection quickly. Values are typical for 4-pole IE2 motors at 415 V, 50 Hz. Always confirm with the current printed on your motor's nameplate. Prices checked 13 October 2026. Reviewed by Amit, Voltkart.

415 V motor full-load current chart (kW, HP and amps)

Motor kW HP Full-load current (415 V) Contactor (AC-3) Overload relay MPCB (up to 15 kW)
0.37 kW 0.5 HP 1.1 A LC1D09
₹1,421
LRD06
₹1,890
GV2ME06
₹4,670
0.55 kW 0.75 HP 1.5 A LC1D09
₹1,421
LRD06
₹1,890
GV2ME06
₹4,670
0.75 kW 1 HP 1.8 A LC1D09
₹1,421
LRD07
₹1,890
GV2ME07
₹4,670
1.1 kW 1.5 HP 2.6 A LC1D09
₹1,421
LRD08
₹1,890
GV2ME08
₹4,830
1.5 kW 2 HP 3.5 A LC1D09
₹1,421
LRD08
₹1,890
GV2ME08
₹4,830
2.2 kW 3 HP 5 A LC1D09
₹1,421
LRD10
₹1,890
GV2ME10
₹4,830
3 kW 4 HP 6.5 A LC1D09
₹1,421
LRD12
₹1,890
GV2ME14
₹4,830
3.7 kW 5 HP 7.5 A LC1D09
₹1,421
LRD14
₹2,120
GV2ME14
₹4,830
5.5 kW 7.5 HP 11 A LC1D12
₹1,600
LRD16
₹2,120
GV2ME16
₹5,410
7.5 kW 10 HP 15 A LC1D18
₹3,152
LRD21
₹2,200
GV2ME20
₹5,850
9.3 kW 12.5 HP 18 A LC1D25
₹2,305
LRD22
₹2,200
GV2ME21
₹6,220
11 kW 15 HP 22 A LC1D25
₹2,305
LRD22
₹2,200
GV2ME22
₹6,220
15 kW 20 HP 29 A LC1D32
₹8,116
LRD32
₹3,510
GV2ME32
₹10,074
18.5 kW 25 HP 35 A LC1D38
₹6,378
LRD35
₹3,510
–
22 kW 30 HP 42 A LC1D50
₹8,850
LRD350
₹5,330
–
30 kW 40 HP 57 A LC1D65
₹12,300
LRD365
₹6,840
–
37 kW 50 HP 70 A LC1D80
₹15,350
LRD3363
₹7,418
–
45 kW 60 HP 85 A LC1D95
₹19,800
LRD3365
₹9,157
–
55 kW 75 HP 103 A LC1D115
₹27,964
– –
75 kW 100 HP 138 A LC1D150
₹32,068
– –

Rule of thumb: about 2 A per kW at 415 V. Contactor and relay pairings are for direct-on-line starting; for star-delta, set the overload relay to about 58% of the full-load current.

Related tools

Motor current FAQs

How do I calculate the full-load current of a 3-phase motor?

Full-load current = kW × 1000 ÷ (√3 × voltage × power factor × efficiency). For a 7.5 kW motor at 415 V with a power factor of about 0.85 and efficiency of about 0.88: 7500 ÷ (1.732 × 415 × 0.85 × 0.88) ≈ 14 A, which is close to the 15 A in the chart. The motor nameplate always gives the exact figure.

Why is the current different on my motor nameplate?

Full-load current depends on the number of poles, efficiency class (IE1, IE2, IE3), power factor and the manufacturer. 2-pole and 6-pole motors and rewound motors can differ from the typical values here, so always set protection to the nameplate current.

What is the current of a 5 HP and a 10 HP motor at 415 V?

A 5 HP (3.7 kW) 3-phase motor draws about 7.5 A, and a 10 HP (7.5 kW) motor about 15 A at 415 V. A rough rule of thumb is about 2 A per kW at 415 V for small and medium motors.

How much current does a motor draw when starting?

A direct-on-line start draws about 6 to 7 times the full-load current for a few seconds. Star-delta starting reduces this to about one-third, and a VFD or soft starter limits it further.

What size contactor and overload relay do I need?

Choose a contactor whose AC-3 rating covers the motor kW, and an overload relay whose setting range includes the full-load current, then set it to the nameplate current. The chart above gives the usual Schneider pairing for 415 V DOL starters.

You are welcome to link to this chart from your own site or course notes.